EDL180

Portable Analyzer

Portable (Class A, Ed. 3) PQ Analyzer

The EDL180 is a portable version of the Class A (Edition 3) PM180 power quality analyzer, which holds extensive track record serving as the platform for power quality monitoring systems in worldwide national grids.
Equipped with a 24V battery for backup power supply and flexible current clamps, it is fitted in a lightweight traveling bag for convenient handling

Power Quality

 

  • EN50160 reports
  • GOST 32144 reports
  • Waveform capture and event recording @ 256 samples/cycle

 

Backup Battery Power

 

Built-in UPS providing over 4 hours of work at maximum consumption

 

Communication

 

  • Built-in: RS485; ETH; IRIG-B
  • Optional ports: 2G/3G
  • Open protocol: IEC 61850; Modbus RTU; DNP3.0; IEC 60870-5-101/104

 

3V AC Current Inputs

 

Supplied with current clamps

 

Voltage Inputs: 690V AC nominal

Power Meter

  • Power: True RMS volts, amps, power, power factor, neutral current, angles and unbalance for voltage and current, frequency, symmetrical components and many more
  • Event and parameter data-logging
  • Sampling frequency: up to 256 samples/cycle

Power Quality

  • NMI certified for Class A, Edition 3, per IEC 61000-4-30
  • EN50160 / GOST 32144 monitoring, statistics & reports
  • Event statistics complimented by waveform recording
    in 8 channels (4 voltage inputs, 4 current inputs) @ 256 samples/cycle
  • V-I angle, THD, TDD and K factor for Voltage and Current and up to the 63rd order harmonic. individual harmonics for V, I, P, Q
  • Including directional power harmonics (Load or Source)
  • Inter-harmonics
  • Disturbance Direction Detection (upstream/downstream)
  • Flicker according to IEC 61000-4-15

Logging, Recording & Programming

  • Programmable controller: up to 64 control setpoints, up to 8 conditions OR, AND, arithmetical functions logic, extensive triggers, programmable thresholds and delays, relay control, event-driven data recording
  • 9 fast waveform recorders: simultaneous 8-channel AC, one DC
  • Waveform sampling rate 32, 64, 128 or 256 samples per cycle
  • Up to 3.5 min. of continuous waveform recording
  • 16 fast Data Recorders (16 parameters on each data log): From ½ cycle RMS to 2 hour RMS envelopes; programmable data logs on a periodic basis and on internal or external trigger
  • ½-cycle response time
  • 32 digital internal counters
  • 16 internal programmable timers (½ cycle to 24 hours)

Current Inputs

  • 3V AC: inputs for generic current clamps (Rogowski)

Voltage Measurement Inputs

Nominal voltage: 690V AC

Operating range: up to 828V AC

 

5th AC/DC voltage input:

up to 300V DC (monitoring substation battery)

Communication interfaces

Built-in:

  • RS-485
  • USB
  • ETH 10/100Base-T
  • IRIG-B

Optional/additional: (1 per device):

  • 3G GSM; incl. 2nd RS485 port

Communication Protocols

  • Modbus
  • ASCII
  • DNP3.0
  • IEC 60870-5-101/104
  • IEC 61850

Display

Graphic color display: 5.7″ touchscreen

Real-Time Clock & Synchronization

  • Real-Time Clock with maximum 5 seconds drift per month @ 25°C
  • Provides 1 msec time resolution via IRIG-B time code input or satellite clock for common time base (requires IRIG-B module)
  • As an SNTP client, it can accept periodic synchronization of the meter clock from an SNTP server

Power Supply

Built-in:

  • 85-265V AC / 88-290V DC
  • Installed UPS backup: over 4 hours of work at full consumption

Enhanced Meter Security

  • 3 levels Password security for protecting meter setups and accumulated data from unauthorized changes
  • Defining up to 20 users in different access levels
  • Extra-complex password is required
  • Access and configuration log is automatically and continuously recorded, documenting all user activity