>  Home >  Products >  PM17x PRO

Multi-function Analyzers

Equipped with a bright LED display, the PM17x PRO Series power quality analyzers combine the familiar look and feel of the PM17x legacy models with the advanced PRO Series capabilities.
To top this, the PM17x PRO analyzers introduce unique features, available only in the PM17x sub-series, such as an IRIG-B
input and a fourth voltage input (Vref).

Featuring multiple protocols (IEC 61850, DNP3 and IEC 60870-5-101/104) and dual-port ethernet, it is the ultimate solution for power monitoring, meeting and exceeding current requirements in utility and industrial applications.

Revenue Meter: Class 0.2/0.2S accuracy
Wide-range Inputs: 1,000V AC

Power Quality

  • Class A, Ed. 3.1 analyzer per IEC 61000-4-30 (PM174/5 PRO)
  • EN50160 reports (PM175 PRO)
  • IEEE 1159 reports (PM174 PRO)
  • IEEE 519 harmonic analysis
  • Waveform capture and recording
  • Up to 0.0001 Hz resolution
  • Leakage current detection via 4th current input

Communication

  • Dual Port Ethernet: RSTP support
  • IEC 61850
  • Open protocol: Modbus RTU; DNP3.0; IEC 60870-5-101/104;

Digital & Analog I/O

Built-in I/O: 1 RO; 2 DI; 1 AI

Multi-option Current Inputs

  • 5A or 1A
  • 40mA for HACS CTs (100-3,000A)
  • RS5: clip-on 5A HACS for retrofit
  • LPIT: RJ45 inputs supporting LPIT Sensors; up to 650A primary current, and a secondary of 80 A/150 mV @ 50 Hz and 80 A/180 mV @ 60 Hz

Multi-Functional 3-Phase Power Meter

  • Voltage, current (including neutral current), power, energy, power factor, frequency, voltage/current unbalance
  • Ampere/Volt demand meter

Power Quality

  • Class A, Ed. 3.1 analyzer
  • EN50160 reports and statistics (PM175: EU version)
  • IEEE 1159 reports and statistics (PM174: US version)
  • Voltage Dips/Sags, Interruptions, Swells, Unbalance, Transient and THD events recording
  • THD of voltage and current, custom alarming, TDD, K factor, Crest factor
  • Individual harmonics, up to the 63rd harmonic
  • IEEE 519 harmonic analysis

Waveform Capture and Recording

  • Provides simultaneous capture for all voltage and current channels with choice of sample rate, up to 256 samples/cycle
  • Selectable pre-fault / post-fault recording length.

Variable Current Inputs

  • Standard 1A or 5A current inputs
  • 40mA inputs, designed for SATEC HACS CTs
  • RS5: Special 5A input for 5A clip-on HACS for retrofit installation on existing MV/HV CT secondary.
  • LPIT: RJ45 inputs supporting LPIT Sensors; up to 650A primary current, and a secondary of 80 A/150 mV @ 50 Hz and 80 A/180 mV @ 60 Hz

Revenue Grade Meter

  • Class 0.2S/0.2 per IEC 62053-22/ANSI 12.20
  • Advanced Time Of Use (TOU) features for complex billing schemes: 16 Energy sources include external digital pulses, up to 4 seasons, 4 daily profiles, 8 Tariffs, flexible automatic calendar

Logging Recording and Programming

  • Onboard memory: 16GB
  • Programmable controller: up to 64 control setpoints, up to 8 conditions OR, AND, arithmetical functions logic, extensive triggers, programmable thresholds and delays, relay control, event-driven data recording
  • Waveform sampling rate 32, 64, 128 or 256 samples per cycle
  • 1-ms resolution for digital inputs
  • 16 fast Data Recorders (16 parameters on each data log): From ½ cycle RMS to 2 hour RMS envelopes; programmable data logs on a periodic basis and on internal or external trigger
  • 32 digital internal counters for counting pulses from external sources and internal events
  • 16 internal programmable timers (½ cycle to 24 hours)

Compliance

The PM17x PRO analyzers are designed to comply with IEC/AS 62052-11, IEC 62053-22/24, IEC 61557-12 (PMD-Sx), EN 50470 and ANSI C12.1/20 standards.

Built-in I/O

  • 1 AI (±1 mA; 0-1 mA; 0-20 mA; 4-20 mA)
  • 1 SSR (100mA/250V AC/DC)
  • 1 DI (DRC, Internally wetted @ 24VDC)

Programmable Logical Controller

  • Embedded programmable controller
  • 64 control set points; programmable thresholds and delays
  • Relay output control

Display

PM17x PRO: 3-row, 7-segment, bright LED display
(2 x 4 characters + 1 x 6 characters)

RPM07x PRO: No display (transducer version)

Real Time Clock

  • Built-in clock and calendar functions
  • Typical error ±15 seconds per month / < 5 minutes/year @ 25˚C
  • 1ms synchronization over SNTP
  • IRIG-B

Power Supply

Default: 100-277V AC / 100-290V DC

optional (DC AUX): 24V DC (9-36V DC)

Communication Ports

  • Standard 2-wire RS-485 serial
  • 2 x ETH 10/100Base-T (Dual Port Ethernet)
  • USB type-C

Communication Protocols

  • IEC 61850
  • Modbus RTU/TCP
  • DNP 3.0/TCP
  • IEC 60870-101/104

Meter Security

  • Three-level Password security for protecting meter setups and accumulated data from unauthorized changes
  • Anti-tamper design

Mounting

  • Panel mount (4” round / 92×92mm square cutouts)
  • DIN-rail mount (RPM07x)

Plug-In Modules & External Accessories

The PRO Series’ modular configuration enables users to assemble a system that meets their specific needs.

Digital & Analog I/O Options

  • Built-in I/O: 2 digital inputs; 1 SSR output; 1 analog input
  • Add-on I/O: Up to 3 add-on I/O modules

Module Configuration

  • Up to 4 Expansion Modules Side by Side
  • Up to 2 expansion modules: self-energized
  • 3 expansion modules: requires additional module of AUX power supply

DC Auxiliary Power Supply

24V DC (9-36V DC)

The PM17x PRO models are identical in physical appearance and mounting/installation, and differ only in functionality

PM175 PRO

Panel-mounted Class A Ed. 3.1 power quality analyzer monitoring voltage, current, power, frequency and energy measurements.

PQ statistics & reports: per the European EN50160 standard

 

PM174 PRO

Panel-mounted Class A Ed. 3.1 power quality analyzer monitoring voltage, current, power, frequency and energy measurements.

PQ statistics & reports: per the U.S. IEEE 1159 standard

 

PM172 PRO

Advanced panel-mounted power meter monitoring voltage, current, power, frequency and energy measurements, combined with power quality analysis and data logging capabilities.

RPM07x PRO

Transducer version (no screen) of the above models

Contact now

one of our experts






    Featured Content